Exciter Model: IEET1B
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Tr < 0.5*Mult*TimeStep then Tr = 0, ElseIf 0.5*Mult*TimeStep < Tr < Mult*TimeStep then Tr = Mult*TimeStep
- If 0.0 < Ta1 < 0.5*Mult*TimeStep then Ta1 = 0, ElseIf 0.5*Mult*TimeStep < Ta1 < Mult*TimeStep then Ta1 = Mult*TimeStep
- If 0.0 < Ta2 < 0.5*Mult*TimeStep then Ta2 = 0, ElseIf 0.5*Mult*TimeStep < Ta1 < Mult*TimeStep then Ta1 = Mult*TimeStep
- If 0 < Te < Mult*TimeStep then Te = Mult*TimeStep
- If 0 < Tf1 < Mult*TimeStep then Tf1 = Mult*TimeStep
- If Vrmax < Vrmin then swap the values
- If Vsmax < Vsmin then swap the values
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| Tr | Transducer time constant, sec |
| Vsmax | Vsmax |
| Vsmin | Vsmin |
| Ka | Voltage regulator gain |
| Ta1 | Voltage regulator time constant, sec |
| Vrmax | Maximum control element output, pu |
| Vrmin | Minimum control element output, pu |
| Ta2 | Voltage regulator time constant, sec |
| KF1 | KF1 |
| Tf1 | Feedback lead time constant, sec |
| Ke | Exciter field resistance line slope margin, pu |
| Te | Exciter field time constant, sec |
| E1 | Field voltage value, 1 |
| SE1 | Saturation factor at E1 |
| E2 | Field voltage value, 2 |
| SE2 | Saturation factor at E2 |
| Switch | 0: Feedback is Efd; 1: Feedback is Vreg |
| Xe | Excitation transformer effective reactance, pu |